3C14(7)MCHL600V3X18GRD VFD

Description

Description

Standards

  • Product
    UL 1569; UL 2225; UL 44

Multi-conductor 14 AWG to 10 AWG: Multiple conductors and composites, with ground
wire(s), continuous corrugated aluminum sheath, PVC jacket.

Construction

Conductor: Bare, annealed copper conforming to ASTM B3 and Class B stranded in
accordance with ASTM B8.


Insulation: Cross linked polyethylene type XHHW-2 per UL 44.


Assembly: Conductors are cabled in concentric layers with or without grounding wire
(s), interstices are filled with suitable non-hygroscopic fillers, as required. A binder tape of synthetic material assembles the core in an essentially round configuration.


Armor: Continuous corrugated aluminum sheath with no more than 0.2% trace copper
providing complete protection against liquid & gas ingress. It also provides excellent
mechanical protection, additional electrostatic shielding, and serves as an easy means of grounding equipment.


Jacket: Overall black polyvinyl chloride jacket per UL 1569, 90ºC temperature rating;
low gas emission; limited flame spread and excellent corrosion resistance.

Conductor Identification

 

Power and control:

Multi-conductor 14 AWG to 10 AWG: Method #1-E2 per ICEA S-73-532

3 conductor 8 AWG to 2 AWG: Method #1-E2 per ICEA S-73-532

3 conductor 1 AWG to 500 kcmil: Method 4 per ICEA S-73-532

2 & 4 conductor 8 AWG to 750 kcmil: Method #4 per ICEA S-73-532

Composite power and control:
Power conductors: Method #4 per ICEA S-73-532
Control conductors: Method #1-E2 per ICEA S-73-532


Bending Radius
Fixed position: 7 x cable overall diameter
During pulling: 12 x cable overall diameter


Specifications
• Meets UL 44, XHHW-2 600 V conductors
• Meets UL 1569 requirements for Type MC, Metal Clad cables
• Meets UL 2225 for Hazardous Locations
• Designated Type MC as per NEC Article 330
• Marked “MC-HL” for installation and use in Class I Division 1 & 2, Class II Division 1 & 2, and Class III Hazardous Locations

 

Product features
• UL approved cables Type MC, 600 V; File No. E47409
• UL approved insulated conductors
• Cables pass UL 1685 and IEEE 383 vertical tray fire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at 210,000 BTU/hr, IEC 332-3 category A fire test, IEEE 1202 and CSA FT4
• Cables are American Bureau of Shipping (ABS) listed as CWC MC Type MC
• Cables exhibit a low temperature rating of -40ºC impact and –40ºC bend with suitable precautions
• Temperature rating of 90ºC dry and wet
• 130ºC emergency rating & 250ºC short circuit rating
• Continuous, impervious metallic sheath corrugated for flexibility, prevents ingress of moisture, gases and liquids
• Aluminum sheath cross-section exceeds requirements of the NEC Section 250.122 for grounding conductor
• Sheath provides good electronic shielding so that Corflex® can be used in certain instrumentation applications when adequately grounded
• Excellent mechanical & physical properties
• Sunlight resistant jacket
• Suitable for direct burial and use in cable tray and embedment in concrete
• LEAD FREE

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Insulation
Cross-linked polyethylene
Insulation colour
Black

Dimensional characteristics

Dimensional characteristics

Approximate Net Weight
297.6 kg/km
Approximate Net Weight
120 lb/kft
Cable Diameter
16.6 mm
Conductor Size (AWG)
14
Conductor diameter
0.654 inches
Number of strands
7

Electrical characteristics

Electrical characteristics

Maximum operating voltage
600 V

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C
Minimum installation temperature
-40 °C

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*